Transformer UPS BFIz

INDUSTRIAL UPS BFIz 1÷500 kVA

 

Industrial UPS BFIz are complex systems made individually for the customer’s needs.

About product

Every industry has its group of devices that play a critical role in a specific industrial process. For these devices, it is necessary to ensure proper power supply parameters to ensure the course of the technological process, regardless of the parameters of the power supply network, and in case of a power supply network voltage failure, to ensure the possibility of uninterrupted continuation of operation within a certain time.

 

This function is fulfilled by the guaranteed power supply system based on the BFIz-type inverter. Industrial UPS consists of a BFIz inverter, SKB static switch, PBI rectifier with batteries, ATS system, and guaranteed voltage switchboard.

Features

Perfectly sinusoidal shape of the output voltage
High stability of output voltage and frequency
• Possibility of operation with 100% unbalanced load (for 3 phase systems)
Ability to start from the battery (Black start)
• Uninterruptible automatic bypass and maintenance bypass
High short-circuit current
Electromagnetic compatibility (EMI filters)
Galvanic isolation of loads from DC sources
Advanced battery charging and supervision system
Independent battery rectifier dedicated to batteries
Protection against battery deep discharge
Small ripples and low level of harmonics in the battery current
• Battery temperature control and battery charging voltage temperature compensatio
Battery charging current control
Overvoltag, overcurrent, short-circuit protection systems, etc.
• Independent drivers and controllers of individual functional systems in order to increase UPS reliability
• Ability to operate with any type of load (both inductive and capacitive)
– cos φ of consumers allowed in the whole possible range

The UPS BFIz is all about ease of use:

  • Central inverter START/STOP switch
  • Front access to control and monitoring elements
  • Clear and friendly communication with the user
  • Front access to power connections and potential-free terminals

Advanced communication between the user and the device:

  • Keyboard, control console with LCD screen and LEDs
  • Potential-free relay contacts
  • Sound signal informing about an emergency situation
  • Data archiving and event buffer
  • Integrated communication interfaces RS485, USB and Ethernet allow for communication using a serial transmission protocol: Modbus RTU, IEC 60870-5-103, IEC 61850, SNMP; APS6000; other

Technical Specification

UPS POWER SUPPLY UNIT
AC supply voltage – primary power supply Ur, VAC

380/400/415

AC supply voltage – backup power supply Ur, VAC

380/400/415

Supply voltage frequency, Hz

50/60

DC supply voltage – external battery Udc, VDC

48/60/110/220/400

MAINS RECTIFIER
AC supply voltage tolerance, %

+10%, -15% Ur

Supply voltage frequency tolerance, %

+/- 10

Technology – diode bridges

Yes

Galvanic isolation AC/DC

Depending on the design version

Input transformer

Yes

Input transformer type

12-pulse or 6-pulse

Possibility of connection for parallel operation

Yes

Design of the rectifier

Modular / cabinet

BATTERY CHARGER
Input voltage tolerance, % Ur

+10, -15

Supply voltage frequency tolerance, %

+/- 10

Battery charging modes:

buffer: 2,2 – 2,4 V/cell
automatic: 2,4 V/cell;
supervised: 2,7 V/cell.

Battery voltage temperature compensation

Yes

Battery charging current limitation

Yes

Battery circuit continuity check

Yes

Technology: Transistor type PBI (forced cooling)

According to the project requirements

BATTERY
Battery technology

VRLA: AGM / GEL / Ni-Cd

Voltage of 1 monoblock

2 V / 6 V / 12 V

INVERTER
Power supply voltage, VDC

48/60/110/220/400

 

DC input voltage tolerance, %

+/- 15

AC output voltage, VAC

220/230/240 (1-phase)

380/400/415 (3-phase)

Voltage stability (static), %

+/- 1

Frequency stability, %

+/- 0,1

Voltage stability (dynamic), %

+/- 5 during 10 ms

The shape of the voltage

Sinusoidal

THDU voltage distortion (linear loads), %

<2

THDU voltage distortion (non-linear loads), %

<5

Short-circuit current

3:1

Crest factor

3:1

Consumer cos φ range

Cos φ ≤ 1 (0 ind. to 0 cap.)

Inverter efficiency, %

>92

Galvanic isolation DC / AC

Yes

Output transformer

Yes

Electromagnetic compatibility

EMI filters

Parallel operation (current equalization, n+1 redundancy)

Yes

Interface

RS-485 / USB / Ethernet

Data archiving / event buffer / FLASH memory

Yes

UPS OUTPUT
UPS output power, kVA

1 – 100 (1-phase)

1 – 500 (3-phase)

Output voltage, VAC

220/230/240 (1-phase)
380/400/415 (3-phase)

Output voltage frequency, Hz

50/60

OPERATION ENVIRONMENT
Operating temperature, ºC

0 to +40

Storage temperature, ºC

-25 to +55

Humidity, %

Max. 85 (without condensation)

Device access

Service and maintenance from the front

Cable entry

From the bottom

Operational height above sea level without changing the ratied parameters, m

1000

Contact us

You are welcome to contact us if you have questions or are interested in our offer.


    kontakt

    Related products