Rectifiers PBI MS

PBI rectifiers are DC power supply units adapted to the needs of industrial plants with high requirements for efficiency, technical parameters, and reliability.

About product

Systems PBI MS have been designed following the modern trends in the field of power electronics. Thanks to the possibility of independent, parallel operation of the modules, we obtain the possibility of redundant mode which ensures uninterrupted charger operation. The functionality of PBI MS systems enables to design of rectifiers with significant output power, as well as more complex systems.

 

PBI-type buffer power supply units are intended for operation in DC uninterruptible power supply systems as a voltage source for consumers and charging batteries with rated voltages of 24VDC, 48VDC, 110VDC, 220VDC, 400VDC, 700VDC, or other compliant with its specification.

 

Rectifiers are designed to supply consumers connected to the battery as well as directly from the power supply unit.

Due to IGBT transistors usage in the power supply converter, it operates with pulse width modulation (PWM) and superacoustic frequency. Rectifier has such features as:

High stability of output voltages and currents
Very low output current and voltage ripple
Small dimensions and weight
Quiet operation
High efficiency

Rectifier provides:

Galvanic isolation from the mains
Battery temperature voltage compensation
Battery charging current limitation
Minimization of the produced interferences due to the application of multi-stage interference filters
Charging and battery cooperation characteristics in accordance with EUROBAT recommendations

The power supply is equipped with a microprocessor (DSP) control system for the inverter operation and battery status control. It has the following protection systems:

  • against overheating of the power circuits,
  • against short-circuit currents,
  • against overvoltage.

Rectifier allows to charge battery in 3 modes:

  • Buffer operation. In this mode, the device supplies power to the battery and/or loads with a voltage of a high level of stability and the required value (usually 2.23 V/cell). The buffering voltage is compensated thermally by means of a thermal probe which is present in standard equipment and which should be placed near the powered battery.
  • Automatic charging. If the battery is discharged completely or partially (for example as a result of a supply voltage failure), the battery should be recharged as soon as possible in order to prepare it to operate in case of another possible failure. Increasing the voltage by some value will make it possible to equalize the charge in the cells. For this reason, the power supply has been equipped with a mode of automatic charging to the voltage of 2,4V/cell.
  • Supervised charging. In case of cooperation with open acid batteries, additional equalizing charging of the battery to the voltage of 2,7V/cell should be performed periodically. In this mode, the voltage value limit is 2,7V/cell, and the charging current is set in a simple manner by means of the keyboard during the operation of the power supply. 

Technical Specification

Enclosure type

Industrial cabinet 19”

ELECTRICAL PARAMETERS
Output voltage, VDC

24/48/60/110/220/400/700

Output current, A

25-3000/10-1500

CONFIGURATION
Autonomous operation

Standard

Autonomous supervision system SAN

Standard

ADDITIONAL INFORMATION
Distribution board

Option

Earth fault control system (KDZ)

Option

Battery control system SAN 5

Option

Built-in ATS

Option

Communication via RS 485 / Modbus

Option

Languages

PL | EN | RUS | CZ

Files

Datasheet
PBI MS

Download

Contact us

You are welcome to contact us if you have questions or are interested in our offer.


    kontakt