Battery monitoring system SAN 5

Microprocessor-based chemical battery monitoring system SAN 5

Product description

The microprocessor-based SAN 5-1 (SAN 5-1.2) monitoring system is designed for continuous monitoring of the state of a chemical battery. The device measures battery voltage and current, battery symmetry voltage, battery and ambient temperature. The measurements are compared with threshold values, and in case of detecting abnormalities in the battery operation, SAN 5-1 signals emergency states. The primary task of the monitoring system is to detect irregularities in the monitored battery and locate the “weakest” cell.

 

A built-in LCD allows user communication
in two modes:
• displaying all measured values and alarm states occurring in the system;
• displaying an intuitive menu for viewing all current measurements, parameters, system status, and alarm buffers.
It also enables configuration of the device and its operating parameters.

 

DESCRIPTION OF THE OPERATION
During operation, the device performs battery voltage measurements. If any of the measured values exceed the warning or alarm threshold, this is indicated by the lighting of an appropriate LED and the activation of a corresponding relay output. The current system status is also displayed as specific messages on the LCD screen. Using the device’s menu function, it is possible to display all detailed data about the monitored battery. Deep discharge status, warnings, and alarms are additionally indicated by LED lights on the device panel. An alarm from the difference in battery voltage halves (symmetry control) is displayed as ΔU.

Features

High operational stability
Intuitive and easy user interface comprising an LCD, keyboard, and LED lights
USB 2.0 port for transferring alarm buffers to portable memory
Remote indication of an alarm state – potential-free relay contacts
Integration capability with other monitoring systems via RS485 link; communication with computers via RS-232 link
Event archiving – recording in permanent memory every occurrence and cessation of alarm states, warnings, whole system data, and changes in its status
Dual measurement system – for whole battery voltage, battery and ambient temperatures, etc., as well as individual cell voltages in the battery chain or battery symmetry
Visualization of the current battery status and event history

Technical specifications:

ELECTRICAL PARAMETERS
DC power supply voltage

220/110/48/24

AC power supply voltage

230/110/48/24

CONFIGURATION
Measurements

Voltages of 24 battery cells, battery current, battery voltage, battery temperature, ambient temperature

Communication

Interface RS 232 or RS 485

ACCESSORIES
Available language versions

PL | EN | RUS | CZ