Product description

HPI 10S 400/230WO converter module is intended for supplying AC receivers of 230 VAC rated voltage. The converter module is supplied by 3×400 VAC/50 Hz. The system is equipped with microprocessor control and converter operation parameters monitoring system.

Features

It may operate with receivers in a wide range of power
High efficiency of the processing system
Short-circuit protection of the converter
Temperature protection of power systems
Comfortable access to connections (from the front)
Microprocessor control and inverter operation parameters monitoring
Ergonomic housing allowing for comfortable assembly in 19” casing
Galvanic separation of input and output circuit
Low level of higher harmonics of the output voltage
Remote indication of an alarm state – potential-free relay contacts
Built-in controller with selectable communication protocol RS-485
(MODBUS, IEC-103, APS)
Special load control algorithm and built-in event buffer

Technical specifications

ELECTRICAL PARAMETERS
AC rated input voltage

3×400/3×380 V

(+10%/- 15% )

Frequency

50/60 Hz

(+/- 10%)

Rated consumption of current

3×16 A

Rated output AC voltage

230 V

(±2%)

Output voltage frequency

50 Hz

(±0,1%)

Output power

10 kVA

Rated output current

44 A

Overload capacity*

1.1In – long-term
1.1-1.25In – 10 minutes
1.25-1.5In – 3 minutes
1.5-2In – 10 seconds
>2In – 1 second

Voltage waveform

sinusoidal

Harmonics content (linear load)

<2%

Scope of cosφ characterising load

0 ind. up to 0 vol.

Total efficiency

>90%

Over-current protection

6 A x IN

Multiplication factor (CF)

3

Contact us

You are welcome to contact us if you have questions or are interested in our offer.